Choosing Oil-to-SF6 and Wall Bushings for Equipment Interfaces
Check oil and gas interfaces, sealing, wall penetration, insulation level and the applicable test plan against equipment drawings.

Air-to-gas capacitive lead-out bushing connecting GIS assemblies to overhead transmission lines.
Match the electrical duty and transformer or wall interface before requesting a design.
IEC 60137 applies to complete AC bushings; confirm edition and model-specific test evidence. Replacement fit requires drawing approval.
| Model | Housing | Rated voltage | Rated current | 1 min power-frequency withstand | Lightning impulse withstand | Cantilever / bending load | Weight |
|---|---|---|---|---|---|---|---|
| FETA-126/630 | Composite | 126 kV | 630 A | 230 kV | 550 kV | 3150 N | 180 kg |
| FETA-170/2000 | Composite | 170 kV | 2000 A | 275 kV | 650 kV | 3150 N | 430 kg |
| FETA-252/3150 | Composite | 252 kV | 3150 A | 460 kV | 1050 kV | 5000 N | 430 kg |
| FETA-363/4000 | Composite | 363 kV | 4000 A | 510 kV | 1175 kV | 5000 N | 1270 kg |
| CET-550/4000 | Porcelain | 550 kV | 4000 A | 740 kV | 1675 kV | 5000 N | 1970 kg |
Dimensions, interfaces and replacement compatibility require approved drawings and technical review.
Gas Leakage Prevention: Triple seal barrier protects GIS gas purity.
Extreme Pollution Resilience: Available with composite silicone shed profile reaching 31mm/kV creepage.
High Cantilever Capability: Resists conductor pull and gale-force wind loading up to 5000N.
Epoxy resin impregnated core with optimized electric field gradation.
Enter your requirements and send them to our sales desk. If online sending is unavailable, you get an email draft instead.

Check oil and gas interfaces, sealing, wall penetration, insulation level and the applicable test plan against equipment drawings.

Compare oil and dry-core construction, mounting, maintenance and model-specific IEC 60137 test evidence before choosing a transformer bushing.

Review field grading, dimensions, impregnation, curing and model-specific dielectric tests when sourcing RIP condenser cores.