Choosing Oil-to-SF6 and Wall Bushings for Equipment Interfaces
Check oil and gas interfaces, sealing, wall penetration, insulation level and the applicable test plan against equipment drawings.

Direct interface connection between power transformers and SF6 GIS switchgear.
Match the electrical duty and transformer or wall interface before requesting a design.
IEC 60137 applies to complete AC bushings; confirm edition and model-specific test evidence. Replacement fit requires drawing approval.
| Model | Type | Rated voltage | Rated current | 1 min power-frequency withstand | Lightning impulse withstand | Switching impulse withstand | Cantilever / bending load | Weight |
|---|---|---|---|---|---|---|---|---|
| ETGD-126/630 | Draw Lead | 126 kV | 630 A | 230 kV | 550 kV | — | 3150 N | 90 kg |
| ETGD-170/1250 | Draw Lead | 170 kV | 1250 A | 275 kV | 650 kV | — | 3150 N | 130 kg |
| ETGD-252/1250 | Draw Lead | 252 kV | 1250 A | 460 kV | 1050 kV | 850 kV | 4000 N | 160 kg |
| ETGD-550/1250~2500 | Draw Lead | 550 kV | 1250~2500 A | 740 kV | 1675 kV | 1175 kV | 4000~5000 N | 290~640 kg |
| ETGD-252/1250 | Bottom Connected | 252 kV | 1250 A | 460 kV | 1050 kV | 850 kV | 4000 N | 190 kg |
| ETGD-550/1250~2500 | Bottom Connected | 550 kV | 1250~2500 A | 740 kV | 1675 kV | 1175 kV | 4000~5000 N | 400~440 kg |
Dimensions, interfaces and replacement compatibility require approved drawings and technical review.
Substation Miniaturization: Compact transformer-to-GIS integration saves up to 40% switchyard area.
Dual-Environment Tightness: Reliable barrier isolating transformer oil from high-pressure SF6 gas.
Dry RIP Core: Partial discharge <= 10pC, tan delta <= 0.005.
High-strength aluminum alloy flange with dual-barrier fluororubber seals separating oil and gas chambers.
Enter your requirements and send them to our sales desk. If online sending is unavailable, you get an email draft instead.

Check oil and gas interfaces, sealing, wall penetration, insulation level and the applicable test plan against equipment drawings.

Use IEC 60137 for applicable complete AC bushings; confirm the edition, rating, type and routine tests, and report identifiers for the offered model.

Compare oil and dry-core construction, mounting, maintenance and model-specific IEC 60137 test evidence before choosing a transformer bushing.