Transformer Bushing Types Explained: OIP, RIP, RIS, Porcelain and Composite

Transformer bushing types explained: condenser vs non-condenser, OIP, RIP and RIS cores, porcelain and composite housings, and what to check under IEC 60137.

Dry bushing category illustration. Dry alone does not identify RIP or RIS.
Dry bushing category illustration. Dry alone does not identify RIP or RIS.

Selection note: use this guide to compare technical requirements. Confirm catalog ranges, typical values and standard clauses against the model, edition and agreed test conditions; project acceptance follows the approved drawings and technical agreement.

On this page

In short

What are the types of transformer bushings? Transformer bushings are classified in two independent ways: by core insulation and by external housing. By core, the main types are non-condenser (solid or bulk) bushings for lower voltages and condenser (capacitance-graded) bushings for higher voltages, built as OIP (oil-impregnated paper), RIP (resin-impregnated paper) or RIS (resin-impregnated synthetic). By housing, common outdoor housings include porcelain and silicone-rubber composite designs. Silicone sheds may be carried on an FRP tube or applied directly to a dry core, depending on the design. A core technology must be specified separately from its housing, for example RIP with composite housing. Choose by voltage, current, interface, mounting angle, environment and maintenance plan.

  • OIP: paper core impregnated with transformer oil; long-established; needs oil and seal monitoring.
  • RIP: paper core impregnated with cured epoxy resin; dry, oil-free core.
  • RIS: synthetic fabric core impregnated with resin; dry core, less sensitive to moisture during handling and storage.
  • Porcelain housing: rigid, inorganic, glazed ceramic.
  • Composite housing: hydrophobic silicone in an appropriate support design; verify mass and fault behaviour by assembly.

Selection note: this guide explains bushing categories. Confirm ratings, interfaces and test evidence for the quoted model and the applicable IEC 60137 edition and clauses.

Condenser vs non-condenser bushings

A non-condenser (solid or bulk) bushing passes a conductor through an insulating structure without embedded condenser grading layers. Designs may use porcelain or resin and may interface with oil or air. This simpler construction is mainly used at distribution and lower transmission voltages.

At higher voltages, the electric field around the conductor must be controlled. A condenser core is wound from insulating layers with interleaved conductive foils, forming concentric capacitors that grade the radial and axial field. Condenser bushings usually provide a test tap for capacitance (C1, C2) and tan delta measurement. OIP, RIP and RIS are the three main condenser core technologies.

OIP bushings (oil-impregnated paper)

Kraft paper and foils are wound, vacuum-dried and impregnated with mineral oil inside a sealed housing. OIP is a widely used, long-established technology.

  • Contains oil inside the bushing. Monitoring includes oil level, seals and, where applicable, oil sampling.
  • Mounting angle is limited by the oil system. Confirm the limit by model.
  • A common choice for replacements that must match an existing installed fleet.

RIP bushings (resin-impregnated paper)

Crepe paper and foils are wound, dried and impregnated with epoxy resin under vacuum, then cured into a solid core. The core is dry and oil-free, so there is no oil sampling of the core. Housing, the oil-side interface and fault protection still determine the risk of the complete assembly.

Some designs permit horizontal or inclined installation. Confirm that by model. Moisture protection and storage requirements are design-specific. Follow the manufacturer packaging, handling and pre-energization checks. For a comparison of the two most common types, see OIP or RIP Transformer Bushing: What Should Buyers Check?.

RIS bushings (resin-impregnated synthetic)

RIS cores use synthetic insulation instead of paper between the capacitive grading layers, impregnated with resin. Hitachi Energy describes synthetic-fabric RIS cores with reduced moisture sensitivity compared with paper-based insulation. This is a technology explanation, not a claim about every design or about EONOVA supply availability.

IEC 60137:2017 explicitly introduces RIS as a bushing category. Confirm the offered core material, storage instructions and complete-bushing test evidence. No RIS supply claim is made here.

Porcelain vs composite housings

Housing choice does not change the core technology. Specify both. Porcelain is a glazed ceramic body. Composite housing is silicone rubber over a supporting tube, or silicone applied directly over a dry core, depending on the design. Compare actual mass. Porcelain is hydrophilic and relies on creepage and shed profile; silicone has a hydrophobic surface.

Porcelain is brittle, so fragment protection has to be reviewed. Composite construction has a different fault behaviour, and that behaviour has to be reviewed from complete-assembly evidence. A composite housing is not evidence that the assembly cannot fail or that fragments cannot be produced. Typical porcelain pairings are OIP or RIP cores. Composite housings are commonly used with RIP or RIS dry cores and also with other designs.

Porcelain vs composite housing comparison for transformer bushings
ItemPorcelain housingComposite housing
MaterialGlazed ceramicSilicone rubber over a supporting tube or directly over a dry core, by design
MassCompare actual design massUsually lighter. Compare actual design mass
Pollution behaviourHydrophilic; relies on creepage and shed profileHydrophobic surface
Fracture behaviourBrittle; can fragment in a severe faultDifferent fault behaviour; review complete-assembly evidence
Typical pairingOIP or RIP coresCommonly RIP or RIS dry cores; also used with other designs

How else are transformer bushings classified?

By application interface: oil-to-air (transformer), oil-to-SF6 (transformer to GIS), oil-to-oil (transformer to cable box), air-to-SF6 (GIS), and wall bushings. By conductor arrangement: draw-lead, draw-rod, or solid (bottom-connected) conductor, selected by rated current and transformer design.

By duty: AC or DC, including HVDC converter transformers and valve halls, and high-current bushings for generator step-up transformers. These names describe the interface or duty. They do not by themselves set the current rating or prove interchangeability.

How to choose a transformer bushing type

Name both the core (OIP, RIP or RIS) and the housing (porcelain or composite), then approve the interface drawing and test plan. The maintenance and fire-risk policy is a project input, covering oil versus a dry core and porcelain versus composite housing. It is not a performance guarantee for any one technology.

Use IEC 60137 bushing standards as the buying checklist, then match the clauses to the offered model.

  • Rated voltage, current, AC or DC duty and insulation level. Distinguish the highest voltage for equipment from the test withstand voltage.
  • Interface: flange, oil-side length, terminal, CT space, and any dimensional standard that covers it, such as EN 50180, EN 50181 or IEEE C57.19.01.
  • Mounting angle and installation envelope.
  • Environment: pollution, creepage, altitude and seismic requirements. Use material- and duty-appropriate IEC TS 60815 guidance, not a single universal creepage figure.
  • Maintenance and fire-risk policy for oil versus a dry core, and for porcelain versus composite housing.
  • Test evidence under the applicable IEC 60137 clauses for the offered model.

Buyer check: name both the core (OIP, RIP or RIS) and the housing (porcelain or composite), then approve the interface drawing and test plan.

EONOVA selection notes

What do the supplied documents establish?

The supplied documents describe OIP condenser transformer bushings and paper-resin dry bushing categories. They also distinguish fiberglass-resin dry designs. The word dry alone does not identify RIP or RIS. Use the OIP and RIP bushings catalogue to start an inquiry, not to establish current supply, test acceptance or an unrestricted voltage range.

Broad header ranges in the supplied summary do not establish every offered model. For the offered model, request its core and housing construction, rated voltage and current, AC or DC duty, interface drawing and matching test records. No RIS supply claim is made here.

Oil-impregnated paper OIP transformer bushing
OIP condenser bushing illustration. Confirm oil system, housing and ratings on the offered drawing.

Related products

Conclusion

Bushing type combines the core insulation (non-condenser, OIP, RIP or RIS) with the housing (porcelain or composite). Select by duty, interface, environment and maintenance plan, and verify model-specific IEC 60137 test evidence.

Discuss your specification

Frequently Asked Questions

What are the main types of transformer bushings?

+

By core: non-condenser and condenser (OIP, RIP, RIS). By housing: porcelain or composite. A bushing is described by both.

What is a condenser bushing?

+

A bushing whose core contains concentric conductive foils that grade the electric field; it is used at higher voltages and usually has a test tap.

What is the difference between OIP and RIP bushings?

+

OIP uses oil-impregnated paper inside a sealed, oil-filled housing; RIP uses paper impregnated with cured epoxy resin, giving a dry core.

What does RIS mean in bushings?

+

Resin-impregnated synthetic: a dry condenser core using synthetic material instead of paper, which is less sensitive to moisture.

Is a composite bushing the same as an RIP bushing?

+

No. "Composite" describes the silicone-rubber housing; "RIP" describes the core. An RIP bushing can have a porcelain or composite housing.

Which standard applies to transformer bushings?

+

IEC 60137 covers insulated bushings for AC voltages above 1000 V. Confirm the contracted edition, application scope and clauses for the offered model.

Source documents

  1. [1]
    1: IEC 60137:2017 Insulated bushings for alternating voltages above 1000 V

    IEC

    Supports: Separately supplied insulated bushings for three-phase AC equipment above 1000 V, 15 to 60 Hz, including the 2018 corrigendum. Other applications, including HVDC, require special agreement. AC limits do not automatically apply to DC. Appearance of a voltage class in the standard is not an EONOVA supply claim.

  2. [2]
    2: Hitachi Energy: Bushing technologies

    Hitachi Energy

    Supports: OIP, RIP and RIS construction and non-condenser examples, including the description of synthetic-fabric RIS cores. Technical context only; its product claims and qualifications are not EONOVA claims.

  3. [3]
    3: OIP Condenser Bushing Catalog (2020), public PDF pages 12 to 17

    Catalogue publisher

    Supports: Supplier model tables for OIP condenser transformer bushings. Not current EONOVA supply or certification evidence, and not a single family voltage ceiling.

  4. [4]
    4: RIP Dry-Type Bushing Catalog (2026), public PDF page 4

    Catalogue publisher

    Supports: The supplier catalogue distinguishes resin-impregnated paper and resin-impregnated fiberglass dry bushing categories. Dry alone does not identify RIP or RIS. This file is not relabelled as an EONOVA factory document, and it is not certification or a current supply list.