How to Specify GIS High-Voltage Test Equipment
Define test voltage, waveform, specimen capacitance, measurement background, space and safety interfaces before requesting a test-system design.

Metal-enclosed SF6 test transformer system directly dockable to GIS with background partial discharge below 0.5pC.
Size the test source around the object, connection and test program.
IEC 60060-1 describes HV test techniques; IEC 60270 describes charge-based PD measurement. Confirm the apparatus test standard separately.
| Parameter | Value |
|---|---|
| Rated High Voltage | 200 kV - 1250 kV (Cascadable to 1500 kV) |
| Rated Capacity | 200 kVA - 2000 kVA |
| Background Partial Discharge | <= 0.5 pC (Field verified 0.3 pC at 1250 kV) |
| Short-Circuit Impedance | <= 5% (Ideal for pollution testing) |
| SF6 Operating Pressure | 0.35 MPa - 0.45 MPa |
| Coupling Interface | Direct GIS Flange / Air-SF6 Bushing / Bushing Tank |
| Control Console | Industrial fiber-optic PLC automated measurement & data logging |
Dimensions, interfaces and replacement compatibility require approved drawings and technical review.
Metal-clad design can limit external corona interference; verify measurement background for the specified setup.
Space-Saving Footprint: Saves 70% floor space compared with open-type test transformers, fitting standard indoor bays.
Direct GIS Docking: Equipped with multi-angle GIS docking flanges and safety interlocked earthing disconnectors.
Enter your requirements and send them to our sales desk. If online sending is unavailable, you get an email draft instead.

Define test voltage, waveform, specimen capacitance, measurement background, space and safety interfaces before requesting a test-system design.

Use IEC 60137 for applicable complete AC bushings; confirm the edition, rating, type and routine tests, and report identifiers for the offered model.

Identify voltage duty, field grading, moisture control, external insulation and altitude corrections in the project specification.