Creepage Distance by Pollution Class: IEC 60815 SPS Table and Worked Examples

Creepage distance by pollution class: IEC 60815 SPS classes a–e, reference USCD in mm/kV, diameter and altitude notes, worked 145, 252 and 550 kV examples.

AI-generated illustration of the shed profile of a composite hollow insulator.
AI-generated illustration of the shed profile of a composite hollow insulator.

Selection note: use this guide to compare technical requirements. Confirm catalog ranges, typical values and standard clauses against the model, edition and agreed test conditions; project acceptance follows the approved drawings and technical agreement.

On this page

In short

How much creepage distance does an insulator need? Under IEC TS 60815, multiply the reference unified specific creepage distance (RUSCD) for the site pollution severity (SPS) class by the highest voltage across the insulator — Um/√3 for phase-to-earth AC insulation — then apply the applicable corrections. A 145 kV phase-to-earth insulator in a heavy (class d) site needs at least about 43.3 × 145/√3 ≈ 3,625 mm before diameter, altitude or profile corrections.

Reference USCD by site pollution severity class
SPS classDescriptionReference USCD (RUSCD), mm/kV of Um/√3Old specific creepage, mm/kV of Um (phase-to-phase)
aVery light22.0— (≈12.7)
bLight27.816
cMedium34.720
dHeavy43.325
eVery heavy53.731
RUSCD values: IEC TS 60815-2, Figure 1 (glass and ceramic insulators, AC). The right-hand column is the older phase-to-phase convention, shown only for conversion (value × √3 ≈ RUSCD).

Selection note: this guide explains the IEC TS 60815 method for outdoor AC insulators. Confirm the standard edition, site pollution data, insulator drawing and correction factors for the actual project; acceptance follows the approved drawing and technical agreement.

What do creepage distance, SCD and USCD mean?

Creepage distance is the shortest path along the insulating surface between the two metal parts (for example, the two flanges of a hollow insulator). It is not the same as air clearance or dry arcing distance: creepage governs pollution performance, while clearance and arcing distance govern impulse and dry withstand. Check both.

Unified specific creepage distance (USCD) is the creepage distance divided by the r.m.s. value of the highest operating voltage across the insulator, in mm/kV. For phase-to-earth insulation in a three-phase AC system this voltage is usually Um/√3.

Specific creepage distance (SCD) is the older convention from IEC/TR 60815:1986, which divided by the phase-to-phase voltage Um. For phase-to-earth insulation, USCD is √3 times the old SCD. This is why older specifications quote 16, 20, 25 or 31 mm/kV while current IEC guidance quotes 27.8, 34.7, 43.3 or 53.7 mm/kV for essentially the same classes.

Practical rule: before comparing any mm/kV figure — on a tender, a datasheet or a catalogue — confirm which voltage it uses as its denominator. A "31 mm/kV" requirement on Um and a "53.7 mm/kV" requirement on Um/√3 describe nearly the same creepage length.

How is the site pollution severity (SPS) class determined?

IEC TS 60815-1 defines five SPS classes, from a – very light to e – very heavy, and gives methods for evaluating site pollution severity. In practice the class is built from three kinds of site information.

The class letters do not correspond one-to-one with the old numbered pollution levels of IEC/TR 60815:1986. If the estimate sits close to the next class up, IEC guidance allows using the curve rather than the bar value — in practice, round up rather than down.

Use this table only as a starting point. A substation's own measurements or a neighbouring line's service record override any generic description.

  • Service experience of insulators already installed at or near the site.
  • Measurement of pollution on reference insulators or monitoring devices — for example equivalent salt deposit density (ESDD) and non-soluble deposit density (NSDD).
  • Estimation from the environment (distance to the coast, industry, agriculture, desert, prevailing wind and rainfall) when no measurements exist.
Environment and SPS tendency (illustrative only)
Environment (illustrative only)Tendency
Rural or mountainous, far from sea and industrya–b
Mixed rural/urban, moderate industry, some sea windc
Coastal, industrial or near heavy trafficd
Very close to the sea, conductive industrial dust, desert with salt and condensatione

Step-by-step: from SPS class to required creepage

Calculate: required creepage = RUSCD × corrections × Um/√3.

  • 1. Fix the voltage basis. Use the highest voltage for equipment Um (for example 145 kV, 252 kV, 550 kV), not the nominal system voltage. For phase-to-earth AC insulation, divide by √3.
  • 2. Read the RUSCD for the SPS class from the table above.
  • 3. Apply the corrections given by the applicable part of IEC TS 60815. Diameter (Kad / Kd): larger-diameter post and hollow insulators perform worse per millimetre of creepage. In the 2008 edition of Part 2, Kad = 1 for average diameter Da below 300 mm and Kad = 0.0005 × Da + 0.85 for Da of 300 mm or more (Da in mm). Altitude (Ka): the 2008 edition treats Ka = 1 in most cases; a correction may be applied for altitudes above about 1,500 m where there is no previous operating experience. The 2025 editions revise the altitude and diameter corrections and add profile (Ks) and parallel-insulator (Kp) corrections — use the edition named in the project specification.
  • 4. Calculate: required creepage = RUSCD × corrections × Um/√3.
  • 5. Round up to the next creepage distance actually available for that insulator type.
  • 6. Check the profile (shed spacing and overhang, creepage-to-clearance ratio, creepage factor) — extra creepage packed into a poor profile does not perform as calculated.
  • 7. Confirm by testing where the risk or the standard demands it (for example artificial pollution tests).

Identify the denominator, round up, then check the profile — not one universal mm/kV figure.

EONOVA selection notes

Required minimum creepage by voltage and class (before corrections)

Calculated as RUSCD × Um/√3 with all correction factors = 1. Values rounded to the nearest millimetre.

These are starting values, not acceptance values. Large hollow insulators often have Da above 300 mm, so the diameter correction usually increases the requirement.

Required minimum creepage by Um and SPS class, before corrections
Um (kV)a – 22.0b – 27.8c – 34.7d – 43.3e – 53.7
72.5921 mm1,164 mm1,452 mm1,812 mm2,248 mm
1261,600 mm2,022 mm2,524 mm3,150 mm3,906 mm
1451,842 mm2,327 mm2,905 mm3,625 mm4,496 mm
1702,159 mm2,729 mm3,406 mm4,250 mm5,271 mm
2523,201 mm4,045 mm5,049 mm6,300 mm7,813 mm
4205,335 mm6,741 mm8,414 mm10,500 mm13,022 mm
5506,986 mm8,828 mm11,019 mm13,750 mm17,052 mm

Worked examples

Example 1 — 145 kV hollow insulator, heavy pollution (class d). Example 2 — 252 kV, very heavy pollution (class e). Example 3 — 550 kV, very heavy pollution (class e).

Example 1 — 145 kV hollow insulator, heavy pollution (class d)

Model check (supplied HCI catalogue table): HCI-145/10 (154 mm inner-diameter group) lists 3,640 mm creepage — just above the uncorrected 3,625 mm but below 3,806 mm if Kad = 1.05. HCI-145/12 lists 3,750 mm; HCI-145/8.8 and HCI-145/18.5 list 4,500 mm; HCI-145/10 in the 198 mm inner-diameter group lists 4,640 mm; HCI-145/16.3 lists 5,000 mm. The decision depends on the real average diameter from the drawing, which the catalogue table does not state.

  • Um/√3 = 145 / 1.732 = 83.7 kV
  • Uncorrected requirement: 43.3 × 83.7 ≈ 3,625 mm
  • If the drawing gives Da = 400 mm: Kad = 0.0005 × 400 + 0.85 = 1.05 → 43.3 × 1.05 = 45.5 mm/kV → ≈ 3,806 mm

Example 2 — 252 kV, very heavy pollution (class e)

Model check: HCI-252/11.5 (7,700 mm) and HCI-252/37.5 (7,650 mm) fall short even before correction. HCI-252/12.5 (7,900 mm) passes uncorrected but not with Kad = 1.10. HCI-252/9 and HCI-252/10 (8,600 mm), HCI-252/30 (8,700 or 8,900 mm, depending on inner diameter) and HCI-252/15 (9,650 mm, 300 mm ID) remain candidates; the margin of 8,600 mm over 8,594 mm is too thin to accept without the drawing's Da.

  • Um/√3 = 252 / 1.732 = 145.5 kV
  • Uncorrected: 53.7 × 145.5 ≈ 7,813 mm
  • With Da = 500 mm: Kad = 1.10 → 59.1 mm/kV → ≈ 8,594 mm

Example 3 — 550 kV, very heavy pollution (class e)

Model check: HCI-550/25-01 (17,000 mm) is 52 mm short even before correction. HCI-550/30 variants list 15,800, 18,500 and 18,755 mm; HCI-550/15 lists 18,800 mm; HCI-550/50 lists 20,000 mm; HCI-550/25-02 lists 21,000 mm. Under the illustrative Kad of 1.20, only the 21,000 mm design clears the requirement. With the real Da, the answer may change — this is why the drawing comes before the model number.

  • Um/√3 = 550 / 1.732 = 317.5 kV
  • Uncorrected: 53.7 × 317.5 ≈ 17,052 mm
  • Large hollow insulators: assume Da = 700 mm for illustration → Kad = 1.20 → 64.4 mm/kV → ≈ 20,462 mm

How to pick an HCI model from the catalogue creepage table

Start from Um and inner diameter (ID). The HCI table groups models by rated voltage Ur and ID (130 mm up to 1,000 mm in the supplied table); the ID must suit the apparatus inside.

USCD column = catalogue creepage ÷ (Ur/√3), before diameter correction. The supplied table lists HCI examples from HCI-40.5/12.5 to HCI-1200/50; these are catalogue references, not confirmation of current availability for every model. See the HCI Hollow Composite Insulator page and the hollow insulators category.

  • 1. Start from Um and inner diameter (ID). The HCI table groups models by rated voltage Ur and ID (130 mm up to 1,000 mm in the supplied table); the ID must suit the apparatus inside.
  • 2. Compute the required creepage for your SPS class and voltage, then add the diameter correction using the average diameter from the drawing.
  • 3. Filter by creepage distance in the table, then by dry arcing distance and lightning impulse / power-frequency withstand for insulation coordination, and by bending load and internal test pressure for mechanical duty.
  • 4. Request the drawing for the shortlisted model and check the profile and average diameter before accepting the creepage figure.
Selected HCI catalogue rows and USCD on Um/√3
HCI model (supplied table)Ur (kV)ID (mm)Creepage (mm)USCD on Um/√3 (mm/kV)
HCI-145/101451543,64043.5
HCI-145/8.81451544,50053.8
HCI-252/302522608,70059.8
HCI-550/3055048615,80049.8
HCI-550/25-0155048617,00053.5
HCI-550/25-0255050021,00066.1

Does a silicone (composite) insulator need less creepage than porcelain?

Not automatically. IEC TS 60815-3 covers polymer insulators for AC systems. Its 2025 edition introduces hydrophobicity transfer material (HTM) and recognises that a reduced creepage distance may be used for HTM insulators — but only within that document's method and with evidence for the actual housing material. Hydrophobicity can be lost temporarily or degrade in service. Specify the creepage the method gives, then treat any reduction as a documented engineering decision. For the material side, see silicone rubber hydrophobicity and pollution flashover and composite vs porcelain insulators for substations.

Common mistakes

Mixing denominators: applying 53.7 mm/kV to Um instead of Um/√3 oversizes by √3; applying 31 mm/kV to Um/√3 undersizes badly.

  • Mixing denominators: applying 53.7 mm/kV to Um instead of Um/√3 oversizes by √3; applying 31 mm/kV to Um/√3 undersizes badly.
  • Using nominal voltage (for example 132 kV) instead of Um (145 kV).
  • Ignoring diameter correction on large hollow insulators.
  • Transferring AC rules to DC: DC insulators are covered by IEC TS 60815-4 and generally need a different approach.
  • Counting creepage on a poor profile: closely spaced or deep sheds can be bridged by arcs or rain.
  • Treating snow and ice as pollution: IEC TS 60815-3 explicitly does not deal with snow or ice on polluted insulators.

Applicable EONOVA equipment

HCI Hollow Composite Insulator — the supplied hollow-insulator catalogue tabulates creepage distance, dry arcing distance, withstand voltages, bending load and test pressure by model from HCI-40.5/12.5 to HCI-1200/50. Confirm the model, drawing and test evidence at inquiry.

Related products

Conclusion

Required creepage follows from four inputs: the SPS class, the correct voltage basis, the corrections in the applicable edition of IEC TS 60815, and the real insulator profile. Calculate first, then choose the model — and confirm average diameter and profile on the drawing. Browse more selection guides or send your site data to an EONOVA engineer.

Discuss your specification

Frequently Asked Questions

How much creepage distance is needed for a 145 kV insulator in heavy pollution?

+

Using IEC TS 60815-2, heavy pollution (SPS class d) has a reference USCD of 43.3 mm/kV on Um/√3. For 145 kV that is about 3,625 mm before corrections. Larger average diameters, high altitude or profile corrections increase this, so confirm against the drawing.

What is the difference between specific creepage distance and USCD?

+

Specific creepage distance (old IEC/TR 60815:1986) divides creepage by the phase-to-phase voltage Um. USCD divides by the voltage across the insulator, normally Um/√3 for phase-to-earth AC. USCD is therefore about √3 times the old value.

What are the IEC 60815 SPS classes?

+

IEC TS 60815-1 defines five site pollution severity classes: a very light, b light, c medium, d heavy and e very heavy. Part 2 gives reference USCD values of 22.0, 27.8, 34.7, 43.3 and 53.7 mm/kV for ceramic and glass insulators.

Is 31 mm/kV the same as 53.7 mm/kV?

+

Practically yes for phase-to-earth insulation. 31 mm/kV is the old very-heavy value on Um; multiplied by √3 it is about 53.7 mm/kV on Um/√3. Always check which voltage a specification uses.

Do composite insulators need less creepage than porcelain?

+

Not by default. IEC TS 60815-3:2025 recognises that a reduced creepage distance may be used for insulators with hydrophobicity transfer material, but this must follow the standard's method and evidence for the actual housing.

Does creepage distance change with altitude?

+

Pollution performance can fall at high altitude. The 2008 edition of IEC TS 60815-2 normally uses no altitude correction but allows one above about 1,500 m without service experience; the 2025 editions revise the correction.

Source documents

  1. [1]
    1: IEC TS 60815-1:2025

    IEC

    Supports: Definitions, SPS evaluation methods and general principles. Parts 2, 3 and 4 cover ceramic and glass AC, polymer AC and DC insulators.

  2. [2]
    2: IEC TS 60815-2:2025

    IEC

    Supports: Ceramic and glass insulators for AC. RUSCD from SPS class. Corrections for altitude, diameter, profile and parallel insulators are revised in edition 2.0.

  3. [3]
    3: IEC TS 60815-2:2008 official preview

    IEC

    Supports: USCD definition (Um/√3 versus the 1986 SCD) and Figure 1 RUSCD values 22.0 / 27.8 / 34.7 / 43.3 / 53.7 mm/kV.

  4. [4]
    4: IEC TS 60815-3:2025

    IEC

    Supports: Polymer insulators for AC. HTM concept and reduced creepage for HTM insulators. Snow and ice are excluded.

  5. [5]
    5: Millan Montalvo et al. (2023), Industrial Data 26(2): 315–347

    Industrial Data

    Supports: Prototype Android application paper that reproduces the 2008 RUSCD table and the Kad expressions (Kad = 1 for Da < 300 mm; 0.0005·Da + 0.85 for Da ≥ 300 mm).

  6. [6]
    6: Hollow Composite and Post Insulators Catalog (2025)

    Catalogue publisher

    Supports: Supplied catalogue, PDF pp. 12–13 (printed pp. 10–11): HCI product specification tables (creepage, dry arcing distance, withstand voltages, bending load, test pressure). Supplier information only.

creepage distance by pollution levelspecific creepage distanceIEC 60815 SPS classUSCD mm/kVRUSCDsite pollution severityhollow composite insulator creepage